• Flame Spread Test Machine, BS 476 Part 7
  • Flame Spread Test Machine, BS 476 Part 7

Flame Spread Test Machine, BS 476 Part 7

After-sales Service: Remote Video Training,Remote Video Training,
Warranty: 1 Year
Transport Package: Plywood Case
Trademark: TESTech
Origin: China
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
  • Overview
  • Product Description
Overview

Basic Info.

Model NO.
FTech-BS476-7
HS Code
903180909

Product Description

Product Description

1  The equipment's construction and test procedure is fully comply as per BS 476 part 7.
2  The frame structure is made of stainless steel which is corrosion-resistant.
3  Electronic ignition, automatic flameout
4  Stainless steel exhaust pipe with detachable part, easy to clean thermocouple.
5  Stainless steel burner: inner diameter 3.0mm, outer diameter 6.4mm;
6  The contact height between the flame and the sample is 75mm ~ 100mm; 7 , Specimen size 885mm x 270mm
8  The radiant panel is installed on the frame and 1250mm above the ground.
9 Radiation device: the size of radiation panel is 850mmx850mm; it is composed of porous refractory block. However, the gas mixture is fully combusted, and its surface will not be combusted;
10 Cooling water flow rate is 12L / min; 11, Gas flow rate 1500 ± 200ml / min.
12 The sample tooling can rotate with the central axis, so that the test surface and the radiation plate are at different angles; the position to be tested and the test position can be flexibly adjusted.
13 Automatically adjust the output power according to the test time

Control system:

1, Independent control cabinet
2, Equipped with 17 "touch screen and Labview control system
3,
Intelligent test, easy to operate

4, Imported gas flowmeter, precise control of gas flow
5, Automatic calibration and control of experimental radiation
6,
Test data can be saved automatically and printed freely

Other
  1. Space required for installing and commissioning:1.3m*0.6m*2m,Weight 400kg.
  2. For Radiant panel: Propane gas is required (customer prepare).
  3. For Pilot burner:Town gas is mentioned in the standard.However,for different cities in China,the percentage is different.Please refer to the local actual percentage.(customer prepare)
Flame Spread Test Machine, BS 476 Part 7Flame Spread Test Machine, BS 476 Part 7

 

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now